Bi-directional Inverter Specification – 2DI-250
Features:
-
Bi-directional inverter (generator and consumer, discharger and charger);
-
Grid coupler for different energy storage devices (e.g. batteries);
-
Dynamic working power (P) and reactive power (Q) control;
-
Current source as answer to the power commands.
Applications:
-
Generation and / or consumer support – time shifting;
-
Consumption and / or generation balancing / ramping support;
-
Generation and /or grid support – maintenance management;
-
Power quality improvement – frequency control, reactive power and voltage control;
-
Behind the meter power management functions.
Technical features
Nominal power
|
250 kW
|
Higher need for power
|
Can be paralleled
|
DC voltage range
|
565 to 740 V
|
DC voltage ripple
|
IEEE compliant
|
AC grid voltage
|
3 * 400 V
|
AC voltage tolerance
|
± 10 %
|
Output frequency
|
50 Hz / 60 Hz
|
Harmonic distorsion, current
|
IEEE compliant
|
PCS efficiency (including transformer)
|
94,0 %
|
Inverter efficiency
|
> 97 % (20 to 100 % load range)
|
Inverter cooling
|
forced air
|
Ambient temperature range
|
0 °C to 40 °C
|
Relative outside humidity
|
0 to 90 %, non-condensed
|
Maximum altitude of implementation
|
2000 m above sea level
|
Inverter noise level
|
70 – 80 dBA
|
Indoor housing
|
1200 * 800 * 2200 mm (w*d*h)
|
Indoor weight (including the grid-tie transformer)
|
1450 kg
|
certified by TÜV Rheinland for the following standards:
Safety of power converters
|
IEC 62109-1:2010
|
Charasteristics of the utility interface
|
IEC 61727:2004
|
Islanding prevention
|
IEC 62116:2008
|
Electromagnetic compatibility (EMC) Immunity Standards
|
EN 61000-6-2:2005
|
Electromagnetic compatibility (EMC) Emission Standards
|
EN 61000-6-4:2007 +A1:2011
|